Solar string and charge controller: does the voltage fit?

How many modules can you connect in series to your charge controller? Enter the module values from the datasheet and the controller limit, and CableDeck calculates the open-circuit voltage in frost like the editor. No sign-up, right in your browser.

How CableDeck calculates

In series, the open-circuit voltages of the modules add up and the current stays the same; in parallel, the currents add up and the voltage stays the same.

The open-circuit voltage rises in the cold. Like the editor, CableDeck adds a fixed 15 % and only compares the result with the controller's maximum PV input voltage. The page does not check the current at the controller or limits from standards.

Frequently asked questions

How many 22 V modules can I connect to a 75 V controller?

Two in series give 44 V open-circuit voltage, 50.6 V with the 15 % frost surcharge: that fits. Three give 66 V, 75.9 V in frost, so 0.9 V too much.

Why does the voltage rise in the cold?

The open-circuit voltage of a solar module increases as the temperature drops; the temperature coefficient in the datasheet says how much. The 15 % surcharge is a fixed assumption of the editor; in very cold places the voltage can be higher.

Does the calculator also check the current or limits from standards?

No. This page only compares the open-circuit voltage with the controller limit, like the connection between solar array and charge controller in the editor. It does not check the current at the controller or limits from standards. Compare the controller's maximum PV input current yourself with the string's short-circuit current from the result.

More calculators: Calculate the wire size · Calculate the fuse size · Energy demand and battery size · Convert AWG ↔ mm² · Solar panel size · Battery size · Inverter size

This page in Deutsch · Español · Français

Note: the results are guideline values for planning. They do not replace an inspection by a qualified electrician.